There is an exhaustive set of guidelines put out by the Singapore Civil Defence Force (SCDF) on fire-safety specifications for warehouses. It meticulously crafts policy recommendations designed to save lives and specifically addresses potential fire hazards in commercial storage spaces or general warehouses.
The SCDF categorizes as general warehouses all “single-storey single-user warehouses, single-storey multi-user warehouses, underground warehouses, multi-storey warehouses with or without basements and warehouse [sic] within other non-industrial buildings.” The SCDF is also quite particular in its definition of general warehouses that are covered by the agency’s fire safety requirements. General warehouses are essentially deemed as all storage spaces for different types of goods. Warehouses for storing chemicals and cold rooms for storing fresh produce and other perishable food items are all considered general warehouses. The same is true for stores with floor areas that exceed 100 square meters. The SCDF mandates compliance for general warehouses to adhere to the guidelines on storage height and provisions for fire safety systems.
This SCDF table shows storage heights and sprinkler system guidelines for the different kinds of general warehouses.
Source: SCDF
Source: SCDF
And here are the key points of the SCDF fire safety requirements for storage rooms and warehouses:
- Depending on the fire protection type and warehouse location, the maximum dimensions of compartments must follow the above Table 1.
- An automatic sprinkler system is required if the compartment size is larger than the maximum size allowed in the above Table 1.
- A store room, one that is not outfitted with a sprinkler protection system, is limited to a maximum storage unit height of four meters.
- The sprinkler system must reach areas that are shielded from the water spray by platforms built for accessing tall racks. As for the platforms to access tall racks, they must be made of materials with the same fire-resistant rating as the structural element of the warehouse.
- The height of racks must not exceed the required clearance under the sprinkler shower heads. There should be a red line, 50mm wide, around the signage that says “No Storage Above This Line.” The lettering size of the signage must be 100mm or bigger.
- Smoke control guidelines for general warehouses are itemized in the above Table 2. And there are three smoke control systems recommended by the SCDF. They are smoke vents, smoke purging systems, and engineered smoke control systems. The fire safety requirements for each type of smoke control system are as follows:
Smoke vents
- preferably permanently open and placed in the “highest unobstructed level along the perimeter walls of the warehouse”
- minimum dimensions for vertical smoke vents: 400mm (length) X 600mm (height)
- minimum dimensions for horizontal smoke vents: 0.25 sq. meters
Smoke purging system
- If there is an automatic sprinkler, a smoke purging system may replace a smoke vent.
Engineered smoke control system
- For compartments whose floor areas exceed 5,000 square meters (aboveground warehouse) or 2,000 square meters (belowground warehouse), an engineered smoke control system is allowed.
- Aside from fire extinguishers, automatic sprinkler systems, and smoke control systems, the SCDF lists the following as additional fire safety requirements:
- exit routes and other means of escape when there is a fire
- structural fire precautions
- external provisions to fight fire
- rising mains
- hose reel system
- electrical fire alarm
- exit lighting
- exit signs
- emergency voice communication system
- fire command center
- lift for use by firefighters
- emergency power supplies